-40%

Dranetz/BMI Task 8000-2/1 Taskcard PP1 Power Platform Energy Analyzer w/Clamps

$ 1837.96

Availability: 84 in stock
  • Brand: Dranetz
  • MPN: 800-2
  • Condition: This unit is sold guaranteed working for 30-days, parts and labor, excluding freight.
  • All returns accepted: ReturnsNotAccepted
  • Model: 8000-2

    Description

    Dranetz/BMI Task 8000-2/1 Taskcard PP1 Power Platform Energy Analyzer w/CT-1000's and 150's
    Comes with a manual and what you see in the pictures. If you don't see it, you probably wont get it.
    Specifications are from Dranetz and may vary slightly due to upgrades, options, or revisions this unit may or may not have.
    This unit is sold guaranteed working for 30-days, parts and labor, excluding freight.
    The Unit's Serial Number Tag Reads:
    Model Number:
    8000-2/1
    Serial Number:
    8000MA063(083)
    Options:
    HUR50 Option - Harmonics/User Reports Option
    Items Included:
    PC-PP1 Software Floppy Disks
    Memory Card
    Qty. 2 CT-1000 Current Clamps - 1000 A, 600 V rms. Serial Numbers: 1000NA057(094) and 1000NA056(094)
    Qty. 3 CT-150 Current Clamps - 150 A, 600 V rms. Serial Numbers: 0150MA099(083), 0150MA100(083), 0150MA068(073)
    Qty. 2: PN: 114013-G1, Channel Measuring Intercommunications Cable - Blue
    Qty. 1: PN: 114013-G2, Channel Measuring Intercommunications Cable - Red
    Qty. 3: PN: 114013-G3, Channel Measuring Intercommunications Cable - Black
    Qty. 1: PN: 114013-G4, Channel Measuring Intercommunications Cable - Blue
    Qty. 1: PN: 114013-G5, Channel Measuring Intercommunications Cable - Yellow
    Qty. 2: PN: 114014-G5, Connect to Safety Ground Cable - Green
    Qty. 6: PN:  115227-G1, Alligator Clip Tips - Black
    RS-232 Cable
    Description:
    The 8000-2 is a total electrical system analyzer which enables you to find electric power inefficiencies. It combines the best features of:
    A true RMS Voltmeter and RMS Clamp-on Ammeter (for effective real time troubleshooting
    Oscilloscope (Scope Mode for real time waveform analysis
    An event monitor (records out-of-limit conditions for any parameter)
    Phase angle meter (analyzes phase imbalances)
    Harmonic distortion analyzer (provides harmonic information as required by IEEE 519 and IEC 555-2)
    Neutral-to-ground monitor
    Motor inrush monitor
    A demand and energy use analyzer
    But with all its power and multi-functionality, the Dranetz 8000-2 is easy to use.  Generally, three types of screens appear: menu selection screens, programming screens, and data screens.
    Make selections from menu screens and enter numerical data for programming screens using  the 8000-2's numeric keypad. Programming and data screens have an option bar containing up to six options across the bottom of the screen. Press the function key below an option to select it.
    Technical Features Specifications:
    Physical:
    7" H x 13" W x 10" D (17.8 cm x 33 cm x 25.4 cm), 20.8 pounds (9.4 kg)
    Environmental:
    Operating:
    5 to 45°C
    Storage:
    -20 to 55°C
    Humidity:
    0% to 90%, non-condensing
    Time Clock:
    Crystal controlled. 1 second resolution. Time display in 24 hr format HH:MM:SS. Accurate to 60 seconds per month.
    Memory:
    512 kbytes of standard RAM, 1 mbytes of program ROM
    Memory Card:
    512 Kbytes to 2 Mbytes depending on the optional card memory capacity.
    Power Requirements:
    Voltage:
    Switch selectable; 90 - 130 or 180 - 250 V RMS
    Frequency:
    47 - 450 Hz
    Consumption:
    30 VA normal operation with no printing, 120 VA max while printing (not including battery charging requirements
    Battery Operation:
    Unit will also operate using a 12 V, 10 A external battery with filtering.
    Battery:
    12 V, 2.5 Ahrs Ni-Cad pack for Uninterruptible Power Supply (UPS) operation (up to 2 hours without printing). Kept recharged while unit operates normally. Estimated life of 2 years. 3 V, 1000 mAhrs Lithium battery for data retention with an estimated life of 2 years (operational), 1 1/2 years (storage).
    Interfaces Specifications:
    Display:
    Type:
    Transflective Liquid Crystal Display (LCD) with Electroluminescent (EL) backlighting.
    Resolution:
    240 x 128 dot matrix.
    Size:
    4.25" x 2.27"
    Printer:
    Type:
    High resolution thermal graphics printer.
    Resolution:
    320 dots per line.
    Speed:
    1 inch per second
    Paper:
    2.36" x 98 feet thermal paper.
    Report Size:
    Approx. 4"
    Serial Port:
    Type:
    One RS232D female 25-pin connector
    Configuration:
    DCE
    Data Rate:
    300 to 9600 baud
    Stop Bits:
    1
    Parity:
    ODD, EVEN, or NONE
    Internal Modem:
    Compatible:
    Bell 103, Bell 212A, V.22, V.22 bus Responds to "AT" command set
    Data Rate:
    300, 1200, 2400 baud (automatic)
    Phone Jack:
    RJ-11C
    FCC Registration:
    B46USA-65156-FA-E
    Ringer Equivalence:
    0.2 A
    Relay Outputs:
    4 relays for external access rated 120 V AC or 30 V DC at 1 amp. Rated as pilot relays.
    Alarm:
    Audible alarm of short (approx 0.1 second) or long (approx 1 second) duration to call attention to an error condition or report trigger, respectively.
    Measurements Specifications:
    Synchronization:
    The 8000-2 uses phase locked synchronous sampling over the frequency ranges of 46 - 64 Hz and 380 - 440 Hz. The sample clock is derived from, and is an exact multiple of, an incoming voltage signal (any valid and available voltage is used). The valid signal for locking must be periodic and greater than 30 V RMS. All accuracy specifications are valid over this frequency range. The unit is also capable of simulating synchronous sampling using an internally generated clock for input frequency in the range of 20 - 450 Hz. The user must enter this desired frequency through the configuration menu.
    Phase:
    The 8000-2 samples all eight channels simultaneously to maintain the phase relationship among them.
    Resolution:
    Presented data is always limited to the display resolution of ±1/2 count. Internal resolution of the 8000-2 allows measuring voltage steps of 0.07 volts. Channel D low range resolution is 0.007 volts. Resolution for current measurements is dependent on which CT probe and which input channel is used.
    Probe
    1
    :
    A, B, C:
    D:
    CT-10
    0.002 Amps
    0.0013 Amps
    CT-150
    0.03 Amps
    0.02 Amps
    CT-300
    0.06 Amps
    0.04 Amps
    CT-1000
    0.18 Amps
    0.12 Amps
    CT-3000
    0.55 Amps
    0.37 Amps
    Environmental:
    All specifications are met at 25°C. Temperature coefficient for the measured parameters is approximately 150 ppm of full scale per degree Celsius.
    Updating:
    Measured parameters are updated once per second.
    Voltage:
    Three voltage channels with a common return. One full differential voltage channel.
    Range:
    10 - 600 V RMS AC or 10 - 600 V DC. Channel D selectable 1 - 60 V RMS or DC
    Crest Factor:
    Maximum 2 at full scale
    Accuracy:
    ±0.1% of reading ±0.01% of full scale
    Current:
    Four independent current input channels
    Range:
    10% - 200% of full scale CT rating on A,B,C. 2% - 100% of full scale CT rating on channel D
    Crest Factor:
    Maximum 3 at full scale A,B,C. Maximum 2 at full scale channel D
    Accuracy:
    ±0.1% of reading ±0.01% of full scale, at fundamental frequency, using Dranetz CT-150, CT-1000, CT-3000 probes only
    Input Resistance:
    Voltage Input:
    2 Mohms
    Current Input:
    150 kohms
    Frequency:
    Fundamental Range:
    30 - 450 Hz
    Accuracy:
    ±0.2% of reading
    Measurement Channels Bandwidth:
    DC - 3 kHz
    Real Power:
    Single Phase:
    Average of instantaneous power samples taken as a product of voltage and current samples. Includes sign to indicate direction.
    Three Phase:
    Calculated as the sum of three phases. Includes sign to indicate direction
    Accuracy:
    ±0.2% of reading ±0.02% of full scale at fundamental frequency.
    Apparent Power (VA):
    Single Phase:
    Calculated as volts RMS times amps RMS
    Three Phase:
    Calculated as vector sum of VAR
    ABC
    and W
    ABC
    . Includes sign to indicate direction.
    Accuracy:
    ±0.2% of reading ±0.02% of full scale at fundamental frequency
    Power Factor:
    Calculated as real power divided by apparent power. Includes sign to indicate leading or lagging load current.
    Accuracy:
    ±0.02 typical
    Relative Power (VAR):
    Single Phase:
    Calculated as vector difference between VA and W. Includes sign to indicate direction.
    Three Phase:
    Calculated as the sum of the three phases. Includes sign to indicate direction.
    Accuracy:
    Dependent on PF value
    Demand:
    Average power during a demand interval in W, VA, or VAR
    Accuracy:
    ±0.2% of reading ±0.02% of full scale at fundamental frequency
    Energy:
    Summation of Watt-Hours for accumulated energy use
    Accuracy:
    ±0.2% of reading ±0.02% of full scale at fundamental frequency
    Updating:
    Computed parameters are updated once per second
    Environmental:
    All specifications are met at 25°C. Temperature coefficient for computed parameters is approximately 300 ppm of full scale per degree Celsius.
    Harmonics Specifications:
    Harmonics:
    The 8000-2 performs a harmonic analysis using a Fast Fourier Transform (FFT) algorithm. The accuracy of any given reading is dependent on several factors including amplitude of the input signal, the distortion level, and the distribution of the individual harmonic  components.
    Updating:
    All harmonic related parameters are updated once every five seconds.
    Total Harmonic Distortion (THD):
    Calculated using the individual harmonic components that result from the FFT.
    Displacement Power Factor (DPF):
    A direct result of the FFT that indicated the phase relationship of voltage to current at the fundamental frequency of a given channel. This value will agree with the (true) power factor only when the signals are pure sine waves.
    Telephone Influence Factor (TIF):
    Calculated as per the ANSI/IEEE Standard 519-1981: "IEEE Guide for Harmonic Control and Reactive Compensation of Static Power Converters."
    Transformer Derating Factor (TDF):
    Calculated as per the ANSI/IEEE Standard CS57.110-1986: "Recommended Practice for Establishing Transformer Capability when Supplying Non-Sinusoidal Line Currents."
    CT150 Probe Specifications:
    Current Range:
    0.2 to 150 A rms
    Current Range for Amplitude Accuracy:
    3 to 150 A rms
    Phase Accuracy*:
    0.2° @ 5 - 150 A rms
    Frequency Range:
    45 Hz to 10 kHz
    Output Signal:
    3 V rms @ 150 A rms
    Maximum Conductor Size:
    0.47" (12 mm)
    Note:
    *:
    Typical at fundamental frequency.
    CT1000 Probe Specifications:
    Current Range:
    1 to 1000 A rms
    Current Range for Amplitude Accuracy:
    50 to 1000 A rms
    Phase Accuracy*:
    0.2° @ 100 - 1000 A rms
    Frequency Range:
    30 Hz to 50 kHz
    Output Signal:
    3 V rms @ 1000 A rms
    Maximum Conductor Size:
    2.17" (55 mm)
    Note:
    *:
    Typical at fundamental frequency.
    For Domestic Customers: Packaging, handling, and order processing included in shipping in all domestic shipments as quoted by the shipping calculator. For International Customers there is a .00 minimum for packaging, handling, and order processing. International shipping to be determined by destination.
    Prior to shipment I will need to know the following information (filled out on a form that I will send you) for International Customers or Packages/Freight being Forwarded internationally. International customers may also be subject to a freight forwarder form if applicable.:
    (1) Are you the end-user of this item?
    (2) If you are not the ultimate end-user of the item, please state the ultimate end user's name.
    (3) What is the ultimate country destination?
    05/07/15